Generating Set Functional Test Report |
||||||||
In accordance with ISO 8528 - 6 2005 |
||||||||
PLANT NUMBER: | E11454 | CE: | ||||||
RATED OUTPUT | KVA | 17.5 | RATING CLASSIFICATION | |||||
KW | 14 | |||||||
PHASE | 3 | |||||||
VOLTS | 400 | PERFORMANCE CLASS | ||||||
AMPS | 26 | (AS DEFINED BY ISO 8528-1) | ||||||
HZ | 50 | |||||||
RPM | 1500 | |||||||
GOVERNOR TYPE | MECHANICAL | COOLING METHOD | LIQUID | |||||
ENGINE MAKE | BUILD NUMBER | GN65732 | ||||||
ENGINE MODEL | SERIAL NUMBER | U993793X | ||||||
ALTERNATOR MAKE | ||||||||
ALTERNATOR MODEL | SERIAL NUMBER | B13G298989 | ||||||
CONTROL PANEL(S) | SERIAL NUMBER(S) | |||||||
SWITCHGEAR | SERIAL NUMBER(S) | |||||||
LOAD TEST RESULTS (AT UNITY POWER FACTOR) | ||||||||
LOAD | HZ | VOLTS | AMPS | KW | ENGINE | OIL | OIL | |
type | % | TEMP | TEMP | PRESS | ||||
DEG C | DEG C | BAR | ||||||
load acceptance | 80% | 50 | 400 | 16 | 12 | 5.1 | ||
standby / prime+10% | 110% | 50 | 400 | 22 | 15 | 82 | 4.33 | |
GENERATING SET ENCLOSURE MECHANICAL PROTECTION AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M) (UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD IN ACCORDANCE WITH ISO8528-10) |
IP | |||||||
75 | ||||||||
AMBIENT TEST CONDITIONS | FUEL/OIL USED | |||||||
ALTITUDE (M) | Sea Level | FUEL SPEC | BS2869A2 | |||||
BAROMETRIC PRESSURE (kpa) | 98.9 101,1 | DENSITY | 101,1 | |||||
TEMPERATURE (Deg c) | 23 | CALORIFIC VALUE | 42.5 MJ/kg | |||||
HUMIDITY (%) | 50 | LUB OIL SPEC | Multigrade | |||||
WIRING DIAGRAMS: | ||||||||
ENGINE | CONTROL PANEL(S) | |||||||
TESTED BY | michael | DATE | 22.04.2016 05.09.2013 |