Generating Set Functional Test Report | 
    ||||||||
            In accordance with ISO 8528 - 6 2005 | 
    ||||||||
| PLANT NUMBER: | E10139 | CE: | ||||||
| RATED OUTPUT | KVA | RATING CLASSIFICATION | PRP | |||||
| KW | ||||||||
| PHASE | 3 | |||||||
| VOLTS | PERFORMANCE CLASS | G1 | ||||||
| AMPS | (AS DEFINED BY ISO 8528-1) | |||||||
| HZ | ||||||||
| RPM | 1500 | |||||||
| GOVERNOR TYPE | MECHANICAL | COOLING METHOD | LIQUID | |||||
| ENGINE MAKE | PERKINS | BUILD NUMBER | GN65732 | |||||
| ENGINE MODEL | 404D-22G | SERIAL NUMBER | U989104T | |||||
| ALTERNATOR MAKE | MECC ALTE | |||||||
| ALTERNATOR MODEL | ECO 28-1LN/4 | SERIAL NUMBER | A1089532 | |||||
| CONTROL PANEL(S) | DSE7120 | SERIAL NUMBER(S) | ||||||
| SWITCHGEAR | SERIAL NUMBER(S) | |||||||
| LOAD TEST RESULTS (AT UNITY POWER FACTOR) | ||||||||
| LOAD | HZ | VOLTS | AMPS | KW | ENGINE | OIL | OIL | |
| type | % | TEMP | TEMP | PRESS | ||||
| DEG C | DEG C | BAR | ||||||
| load acceptance | % | 51 | 415 | 18 | 13 | - | - | 5.2 | 
| standby / prime+10% | 110% | 50 | 415 | 25 | 18 | 82 | - | 4.2 | 
| 
            GENERATING SET ENCLOSURE MECHANICAL PROTECTION AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M) (UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD IN ACCORDANCE WITH ISO8528-10)  | 
        IP | |||||||
| 65 | ||||||||
| AMBIENT TEST CONDITIONS | FUEL/OIL USED | |||||||
| ALTITUDE (M) | Sea Level | FUEL SPEC | BS2869A2 | |||||
| BAROMETRIC PRESSURE (kpa) | 98.9 103.7 | DENSITY | 103.7 | |||||
| TEMPERATURE (Deg c) | 3 | CALORIFIC VALUE | 42.5 MJ/kg | |||||
| HUMIDITY (%) | 95 | LUB OIL SPEC | Multigrade | |||||
| WIRING DIAGRAMS: | ||||||||
| ENGINE | CONTROL PANEL(S) | |||||||
| TESTED BY | hwalsh | DATE | 22.04.2016 01.03.2011 | |||||