Generating Set Functional Test Report |
||||||||
In accordance with ISO 8528 - 6 2005 |
||||||||
PLANT NUMBER: | E12332 | CE: | NO | |||||
RATED OUTPUT | KVA | 8.0 | RATING CLASSIFICATION | PRP | ||||
KW | 6.4 | |||||||
PHASE | 1 | |||||||
VOLTS | 230 | PERFORMANCE CLASS | G1 | |||||
AMPS | 35 | (AS DEFINED BY ISO 8528-1) | ||||||
HZ | 50.0 | |||||||
RPM | 1500 | |||||||
GOVERNOR TYPE | MECHANICAL | COOLING METHOD | LIQUID | |||||
ENGINE MAKE | PERKINS | BUILD NUMBER | GJ66043 | |||||
ENGINE MODEL | 403D-11G | SERIAL NUMBER | U135767V | |||||
ALTERNATOR MAKE | STAMFORD | |||||||
ALTERNATOR MODEL | PO44F | SERIAL NUMBER | B11I397455 | |||||
CONTROL PANEL(S) | 7120 MKII | SERIAL NUMBER(S) | ||||||
SWITCHGEAR | SERIAL NUMBER(S) | |||||||
LOAD TEST RESULTS (AT UNITY POWER FACTOR) | ||||||||
LOAD | HZ | VOLTS | AMPS | KW | ENGINE | OIL | OIL | |
type | % | TEMP | TEMP | PRESS | ||||
DEG C | DEG C | BAR | ||||||
load acceptance | 80% | 50.6 | 230 | 22 | 5.1 | 4.8 | ||
standby / prime+10% | 110% | 50.0 | 230 | 31 | 7.0 | 73 | 4.1 | |
GENERATING SET ENCLOSURE MECHANICAL PROTECTION AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M) (UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD IN ACCORDANCE WITH ISO8528-10) |
IP | |||||||
AMBIENT TEST CONDITIONS | FUEL/OIL USED | |||||||
ALTITUDE (M) | Sea Level | FUEL SPEC | BS2869A2 | |||||
BAROMETRIC PRESSURE (kpa) | 98.9 99.8 | DENSITY | 99.8 | |||||
TEMPERATURE (Deg c) | 7 | CALORIFIC VALUE | 42.5 MJ/kg | |||||
HUMIDITY (%) | 83 | LUB OIL SPEC | Multigrade | |||||
WIRING DIAGRAMS: | ||||||||
ENGINE | CONTROL PANEL(S) | |||||||
TESTED BY | ijohnson | DATE | 22.04.2016 10.03.2016 |