Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E13178 CE: NO
RATED OUTPUT KVA 9.0 RATING CLASSIFICATION PRP
KW 7.2
PHASE 3
VOLTS 380/220 PERFORMANCE CLASS G1
AMPS 13.7 (AS DEFINED BY ISO 8528-1)
HZ 50.0
RPM 1500
GOVERNOR TYPE MECHANICAL COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER GJ65605
ENGINE MODEL 403D-11G SERIAL NUMBER U184119C
ALTERNATOR MAKE MECC-ALTE
ALTERNATOR MODEL ECP28-0/S4 SERIAL NUMBER 0001754232
CONTROL PANEL(S) 7120MKII SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 50.4 380 10.9 5.8 4.4
standby / prime+10% 110% 50.0 380 12.1 7.9 73 4.1
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 101.6 DENSITY 101.6
TEMPERATURE (Deg c) 14 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 82 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY ijohnson DATE 22.04.2016 09.05.2018