Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E13166 CE: YES
RATED OUTPUT KVA 7.5 RATING CLASSIFICATION PRP
KW 6.0
PHASE 1
VOLTS 230 PERFORMANCE CLASS G1
AMPS 33 (AS DEFINED BY ISO 8528-1)
HZ 50.0
RPM 1500
GOVERNOR TYPE MECHANICAL COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER GJ65605
ENGINE MODEL 403D-11G SERIAL NUMBER U183779C
ALTERNATOR MAKE STAMFORD
ALTERNATOR MODEL PI044F SERIAL NUMBER B17B072609
CONTROL PANEL(S) 7110MKII SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 50.4 230 21.1 4.8 4.1
standby / prime+10% 110% 50.0 230 29.0 6.6 73 3.8
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 101.6 DENSITY 101.6
TEMPERATURE (Deg c) 8 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 83 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY ijohnson DATE 22.04.2016 25.04.2018