Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E11073 CE: NO
RATED OUTPUT KVA 60 RATING CLASSIFICATION PRP
KW 48
PHASE 3
VOLTS 400/230 PERFORMANCE CLASS G1
AMPS 86 (AS DEFINED BY ISO 8528-1)
HZ 50
RPM 1500
GOVERNOR TYPE ELECTRONIC COOLING METHOD WATER
ENGINE MAKE PERKINS BUILD NUMBER DK51436
ENGINE MODEL 1103A-33TG2 SERIAL NUMBER U323967W
ALTERNATOR MAKE STAMFORD
ALTERNATOR MODEL UCI224E SERIAL NUMBER A11C130039
CONTROL PANEL(S) DSE 7120 SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 52 400 58 40 5.5
standby / prime+10% 110% 50 400 76 52 80 4.3
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
75
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 106 DENSITY 106
TEMPERATURE (Deg c) 19 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 70 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY michael DATE 22.04.2016 05.09.2012