Generating Set Functional Test Report |
||||||||
In accordance with ISO 8528 - 6 2005 |
||||||||
| PLANT NUMBER: | E11886/B | CE: | NO | |||||
| RATED OUTPUT | KVA | 45 | RATING CLASSIFICATION | PRP | ||||
| KW | 36 | |||||||
| PHASE | 3 | |||||||
| VOLTS | 400/230 | PERFORMANCE CLASS | G1 | |||||
| AMPS | 65 | (AS DEFINED BY ISO 8528-1) | ||||||
| HZ | 50.0 | |||||||
| RPM | 1500 | |||||||
| GOVERNOR TYPE | MECHANICAL | COOLING METHOD | LIQUID | |||||
| ENGINE MAKE | PERKINS | BUILD NUMBER | DK51435 | |||||
| ENGINE MODEL | 1103A-33TG1 | SERIAL NUMBER | U409808Y | |||||
| ALTERNATOR MAKE | MECC-ALTE | |||||||
| ALTERNATOR MODEL | ECO32-1L/4 | SERIAL NUMBER | 0001784218 | |||||
| CONTROL PANEL(S) | 7120 | SERIAL NUMBER(S) | ||||||
| SWITCHGEAR | SERIAL NUMBER(S) | |||||||
| LOAD TEST RESULTS (AT UNITY POWER FACTOR) | ||||||||
| LOAD | HZ | VOLTS | AMPS | KW | ENGINE | OIL | OIL | |
| type | % | TEMP | TEMP | PRESS | ||||
| DEG C | DEG C | BAR | ||||||
| load acceptance | 80% | 50.6 | 401 | 42 | 29 | 5.4 | ||
| standby / prime+10% | 110% | 50.0 | 400 | 57 | 40 | 83 | 4.4 | |
|
GENERATING SET ENCLOSURE MECHANICAL PROTECTION AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M) (UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD IN ACCORDANCE WITH ISO8528-10) |
IP | |||||||
| AMBIENT TEST CONDITIONS | FUEL/OIL USED | |||||||
| ALTITUDE (M) | Sea Level | FUEL SPEC | BS2869A2 | |||||
| BAROMETRIC PRESSURE (kpa) | 98.9 101.4 | DENSITY | 101.4 | |||||
| TEMPERATURE (Deg c) | 14 | CALORIFIC VALUE | 42.5 MJ/kg | |||||
| HUMIDITY (%) | 73 | LUB OIL SPEC | Multigrade | |||||
| WIRING DIAGRAMS: | ||||||||
| ENGINE | CONTROL PANEL(S) | |||||||
| TESTED BY | ijohnson | DATE | 22.04.2016 15.10.2014 | |||||