Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E11409/B CE: NO
RATED OUTPUT KVA 45 RATING CLASSIFICATION PRP
KW 36
PHASE 3
VOLTS 400/230 PERFORMANCE CLASS G1
AMPS 64 (AS DEFINED BY ISO 8528-1)
HZ 50
RPM 1500
GOVERNOR TYPE MECHANICAL COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER DK51435
ENGINE MODEL 1103A-33TG1 SERIAL NUMBER U370393X
ALTERNATOR MAKE MECC-ALTE
ALTERNATOR MODEL ECO32-1L/4 SERIAL NUMBER 0001687711
CONTROL PANEL(S) DSE 7120 SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 50 400 46 33 - - 5.04
standby / prime+10% 110% 50 400 56 39 84 - 3.44
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
85
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 102.4 DENSITY 102.4
TEMPERATURE (Deg c) 19 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 65 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY michael DATE 22.04.2016 19.07.2013