Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E10526 CE: NO
RATED OUTPUT KVA 49,5 RATING CLASSIFICATION ESP
KW 39,6
PHASE 3
VOLTS 400/230 PERFORMANCE CLASS G1
AMPS 71,4 (AS DEFINED BY ISO 8528-1)
HZ 50
RPM 1500
GOVERNOR TYPE MECHANICAL COOLING METHOD WATER
ENGINE MAKE PERKINS BUILD NUMBER DK51435
ENGINE MODEL 1103A-33TG1 SERIAL NUMBER U283937V
ALTERNATOR MAKE MECC ALTE
ALTERNATOR MODEL ECO32-1L/4 SERIAL NUMBER 0001502912
CONTROL PANEL(S) DSE 7120 SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 50,4 400 51,3 35,6 84 5,0
standby / prime+10% 110% 50.0 400 57,1 39,6 4,4
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 101,1 DENSITY 101,1
TEMPERATURE (Deg c) 17 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 39 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY lzawierowski DATE 22.04.2016 09.06.2011