Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E0 CE: NO
RATED OUTPUT KVA 45 RATING CLASSIFICATION PRP
KW 36
PHASE 3
VOLTS 400/230 PERFORMANCE CLASS G1
AMPS 65 (AS DEFINED BY ISO 8528-1)
HZ 50
RPM 1500
GOVERNOR TYPE MECHANICAL COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER DK32037
ENGINE MODEL 1103A-33TG1 SERIAL NUMBER U507789D
ALTERNATOR MAKE STAMFORD
ALTERNATOR MODEL UCI224D SERIAL NUMBER C17C101158
CONTROL PANEL(S) DSE 7120MKII SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 50.9 400 47 32 5.2
standby / prime+10% 110% 50.0 400 57 40 81 4.1
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 100.8 DENSITY 100.8
TEMPERATURE (Deg c) 7 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 97 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY hwalsh DATE 22.04.2016 13.04.2018