Generating Set Functional Test Report |
||||||||
In accordance with ISO 8528 - 6 2005 |
||||||||
PLANT NUMBER: | E13155 | CE: | NO | |||||
RATED OUTPUT | KVA | 45 | RATING CLASSIFICATION | PRP | ||||
KW | 36 | |||||||
PHASE | 1 | |||||||
VOLTS | 240/120 | PERFORMANCE CLASS | G1 | |||||
AMPS | 188 | (AS DEFINED BY ISO 8528-1) | ||||||
HZ | 60.0 | |||||||
RPM | 1800 | |||||||
GOVERNOR TYPE | MECHANICAL | COOLING METHOD | LIQUID | |||||
ENGINE MAKE | PERKINS | BUILD NUMBER | DK32037 | |||||
ENGINE MODEL | 1103A-33TG1 | SERIAL NUMBER | U507506D | |||||
ALTERNATOR MAKE | STAMFORD | |||||||
ALTERNATOR MODEL | UCI224E | SERIAL NUMBER | C17K465712 | |||||
CONTROL PANEL(S) | 7120MKII | SERIAL NUMBER(S) | ||||||
SWITCHGEAR |
|
SERIAL NUMBER(S) | ||||||
LOAD TEST RESULTS (AT UNITY POWER FACTOR) | ||||||||
LOAD | HZ | VOLTS | AMPS | KW | ENGINE | OIL | OIL | |
type | % | TEMP | TEMP | PRESS | ||||
DEG C | DEG C | BAR | ||||||
load acceptance | % | 60.5 | 240 | 120 | 29 | 5.9 | ||
standby / prime+10% | 110% | 60.0 | 240 | 165 | 40 | 82 | 4.2 | |
GENERATING SET ENCLOSURE MECHANICAL PROTECTION AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M) (UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD IN ACCORDANCE WITH ISO8528-10) |
IP | |||||||
75 | ||||||||
AMBIENT TEST CONDITIONS | FUEL/OIL USED | |||||||
ALTITUDE (M) | Sea Level | FUEL SPEC | BS2869A2 | |||||
BAROMETRIC PRESSURE (kpa) | 98.9 101.7 | DENSITY | 101.7 | |||||
TEMPERATURE (Deg c) | 12 | CALORIFIC VALUE | 42.5 MJ/kg | |||||
HUMIDITY (%) | 86 | LUB OIL SPEC | Multigrade | |||||
WIRING DIAGRAMS: | ||||||||
ENGINE | CONTROL PANEL(S) | |||||||
TESTED BY | ijohnson | DATE | 22.04.2016 19.04.2018 |