Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E13125/C CE: NO
RATED OUTPUT KVA 40 RATING CLASSIFICATION PRP
KW 32
PHASE 3
VOLTS 415/240 PERFORMANCE CLASS G1
AMPS 56 (AS DEFINED BY ISO 8528-1)
HZ 50.0
RPM 1500
GOVERNOR TYPE MECHANICAL COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER DK32037
ENGINE MODEL 404D-22G SERIAL NUMBER U507596D
ALTERNATOR MAKE STAMFORD
ALTERNATOR MODEL S1L2-K1 SERIAL NUMBER B18A040206
CONTROL PANEL(S) 7120MKII SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 50.4 415 36 26 5.9
standby / prime+10% 110% 50.0 415 49 35 81 4.3
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
85
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 100.3 DENSITY 100.3
TEMPERATURE (Deg c) 5 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 78 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY ijohnson DATE 22.04.2016 07.03.2018