Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E12759 CE: NO
RATED OUTPUT KVA 50 RATING CLASSIFICATION PRP
KW 40
PHASE 1
VOLTS 230/115 PERFORMANCE CLASS G1
AMPS 218 (AS DEFINED BY ISO 8528-1)
HZ 60.0
RPM 1800
GOVERNOR TYPE MECHANICAL COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER DK32037
ENGINE MODEL 1103A-33TG1 SERIAL NUMBER U487010C
ALTERNATOR MAKE STAMFORD
ALTERNATOR MODEL UCI224F SERIAL NUMBER A15D155073
CONTROL PANEL(S) 7110 SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 60.5 230 140 32 5.8
standby / prime+10% 110% 60.0 230 192 44 78 3.7
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
85
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 101.2 DENSITY 101.2
TEMPERATURE (Deg c) 8 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 82 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY ijohnson DATE 22.04.2016 27.04.2017