Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E9744 CE:
RATED OUTPUT KVA RATING CLASSIFICATION PRP
KW
PHASE
VOLTS PERFORMANCE CLASS G1
AMPS (AS DEFINED BY ISO 8528-1)
HZ
RPM
GOVERNOR TYPE MECHANICAL COOLING METHOD
ENGINE MAKE PERKINS BUILD NUMBER DJ51434
ENGINE MODEL 1103A-33G SERIAL NUMBER U243309U
ALTERNATOR MAKE STAMFORD
ALTERNATOR MODEL PI44F SERIAL NUMBER B10H307522
CONTROL PANEL(S) 7110 SERIAL NUMBER(S) 3027013
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 50.4 400 28 19.4 4.9
standby / prime+10% 110% 50 400 34.3 23.7 83 4.6
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
75
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 99.5 DENSITY 99.5
TEMPERATURE (Deg c) 16 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 94 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY ijohnson DATE 22.04.2016 23.08.2010