Generating Set Functional Test Report |
||||||||
In accordance with ISO 8528 - 6 2005 |
||||||||
PLANT NUMBER: | E11314/B | CE: | NO | |||||
RATED OUTPUT | KVA | 36 | RATING CLASSIFICATION | PRP/ESP | ||||
KW | 28 | |||||||
PHASE | 3 | |||||||
VOLTS | 220/127 | PERFORMANCE CLASS | G1 | |||||
AMPS | 94 | (AS DEFINED BY ISO 8528-1) | ||||||
HZ | 60.0 | |||||||
RPM | 1500 | |||||||
GOVERNOR TYPE | MECHANICAL | COOLING METHOD | LIQUID | |||||
ENGINE MAKE | PERKINS | BUILD NUMBER | DJ51434 | |||||
ENGINE MODEL | 1103A-33G | SERIAL NUMBER | U341595W | |||||
ALTERNATOR MAKE | MECC-ALTE | |||||||
ALTERNATOR MODEL | ECP32-2S/4 | SERIAL NUMBER | 0001580556 | |||||
CONTROL PANEL(S) | DSE 7120 | SERIAL NUMBER(S) | ||||||
SWITCHGEAR | SERIAL NUMBER(S) | |||||||
LOAD TEST RESULTS (AT UNITY POWER FACTOR) | ||||||||
LOAD | HZ | VOLTS | AMPS | KW | ENGINE | OIL | OIL | |
type | % | TEMP | TEMP | PRESS | ||||
DEG C | DEG C | BAR | ||||||
load acceptance | % | 60.0 | 220 | 37 | 15 | 5.9 | ||
standby / prime+10% | 110% | 60.0 | 220 | 83 | 32 | 83 | 4.5 | |
GENERATING SET ENCLOSURE MECHANICAL PROTECTION AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M) (UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD IN ACCORDANCE WITH ISO8528-10) |
IP | |||||||
AMBIENT TEST CONDITIONS | FUEL/OIL USED | |||||||
ALTITUDE (M) | Sea Level | FUEL SPEC | BS2869A2 | |||||
BAROMETRIC PRESSURE (kpa) | 98.9 100.0 | DENSITY | 100.0 | |||||
TEMPERATURE (Deg c) | 12 | CALORIFIC VALUE | 42.5 MJ/kg | |||||
HUMIDITY (%) | 62 | LUB OIL SPEC | Multigrade | |||||
WIRING DIAGRAMS: | ||||||||
ENGINE | CONTROL PANEL(S) | |||||||
TESTED BY | grustill | DATE | 22.04.2016 19.04.2013 |