Generating Set Functional Test Report |
||||||||
In accordance with ISO 8528 - 6 2005 |
||||||||
| PLANT NUMBER: | E10765 | CE: | NO | |||||
| RATED OUTPUT | KVA | 27.5 | RATING CLASSIFICATION | PRP | ||||
| KW | 22 | |||||||
| PHASE | 3 | |||||||
| VOLTS | 400/230 | PERFORMANCE CLASS | G1 | |||||
| AMPS | 40 | (AS DEFINED BY ISO 8528-1) | ||||||
| HZ | 50 | |||||||
| RPM | 1500 | |||||||
| GOVERNOR TYPE | MECHANICAL | COOLING METHOD | LIQUID | |||||
| ENGINE MAKE | PERKINS | BUILD NUMBER | DJ51434 | |||||
| ENGINE MODEL | 1103A-33G | SERIAL NUMBER | U304156V | |||||
| ALTERNATOR MAKE | STAMFORD | |||||||
| ALTERNATOR MODEL | PI144F | SERIAL NUMBER | 0269420/029 | |||||
| CONTROL PANEL(S) | 7120 | SERIAL NUMBER(S) | 3252203 | |||||
| SWITCHGEAR |
|
SERIAL NUMBER(S) | ||||||
| LOAD TEST RESULTS (AT UNITY POWER FACTOR) | ||||||||
| LOAD | HZ | VOLTS | AMPS | KW | ENGINE | OIL | OIL | |
| type | % | TEMP | TEMP | PRESS | ||||
| DEG C | DEG C | BAR | ||||||
| load acceptance | % | 50.4 | 400 | 26 | 17.6 | 4.7 | ||
| standby / prime+10% | 110% | 50.0 | 400 | 35 | 24.2 | 80 | 4.4 | |
|
GENERATING SET ENCLOSURE MECHANICAL PROTECTION AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M) (UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD IN ACCORDANCE WITH ISO8528-10) |
IP | |||||||
| 75 | ||||||||
| AMBIENT TEST CONDITIONS | FUEL/OIL USED | |||||||
| ALTITUDE (M) | Sea Level | FUEL SPEC | BS2869A2 | |||||
| BAROMETRIC PRESSURE (kpa) | 98.9 101.2 | DENSITY | 101.2 | |||||
| TEMPERATURE (Deg c) | 3 | CALORIFIC VALUE | 42.5 MJ/kg | |||||
| HUMIDITY (%) | 88 | LUB OIL SPEC | Multigrade | |||||
| WIRING DIAGRAMS: | ||||||||
| ENGINE | CONTROL PANEL(S) | |||||||
| TESTED BY | ijohnson | DATE | 22.04.2016 31.01.2012 | |||||