Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E10570/A CE: NO
RATED OUTPUT KVA 30 RATING CLASSIFICATION PRP
KW 24
PHASE 3
VOLTS 400/230 PERFORMANCE CLASS G1
AMPS 43,3 (AS DEFINED BY ISO 8528-1)
HZ 50
RPM 1500
GOVERNOR TYPE MECHANICAL COOLING METHOD WATER
ENGINE MAKE PERKINS BUILD NUMBER DJ51434
ENGINE MODEL 1103A-33G SERIAL NUMBER U285439V
ALTERNATOR MAKE MECC ALTE
ALTERNATOR MODEL ECO28-VL/4 SERIAL NUMBER 0001505720
CONTROL PANEL(S) DSE 7120 SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 50,7 400 31,1 21,6 5,0
standby / prime+10% 110% 50.0 400 38,1 26,4 82 4,4
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 100,7 DENSITY 100,7
TEMPERATURE (Deg c) 17 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 55 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY lzawierowski DATE 22.04.2016 16.06.2011