Generating Set Functional Test Report |
||||||||
In accordance with ISO 8528 - 6 2005 |
||||||||
PLANT NUMBER: | E10545 | CE: | NO | |||||
RATED OUTPUT | KVA | 31 | RATING CLASSIFICATION | PRP | ||||
KW | 24,8 | |||||||
PHASE | 2 | |||||||
VOLTS | 230/115 | PERFORMANCE CLASS | G1 | |||||
AMPS | 135 | (AS DEFINED BY ISO 8528-1) | ||||||
HZ | 60 | |||||||
RPM | 1800 | |||||||
GOVERNOR TYPE | MECHANICAL | COOLING METHOD | WATER | |||||
ENGINE MAKE | PERKINS | BUILD NUMBER | DJ51434 | |||||
ENGINE MODEL | 1103A-33G | SERIAL NUMBER | U287571V | |||||
ALTERNATOR MAKE | MECC ALTE | |||||||
ALTERNATOR MODEL | ECO32-2L/4 | SERIAL NUMBER | 0001499651 | |||||
CONTROL PANEL(S) | DSE7110 | SERIAL NUMBER(S) | ||||||
SWITCHGEAR | SERIAL NUMBER(S) | |||||||
LOAD TEST RESULTS (AT UNITY POWER FACTOR) | ||||||||
LOAD | HZ | VOLTS | AMPS | KW | ENGINE | OIL | OIL | |
type | % | TEMP | TEMP | PRESS | ||||
DEG C | DEG C | BAR | ||||||
load acceptance | % | 60,4 | 230 | 96,9 | 22,3 | 83 | 4,9 | |
standby / prime+10% | 110% | 60,0 | 230 | 118,2 | 27,2 | 4,3 | ||
GENERATING SET ENCLOSURE MECHANICAL PROTECTION AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M) (UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD IN ACCORDANCE WITH ISO8528-10) |
IP | |||||||
75 | ||||||||
AMBIENT TEST CONDITIONS | FUEL/OIL USED | |||||||
ALTITUDE (M) | Sea Level | FUEL SPEC | BS2869A2 | |||||
BAROMETRIC PRESSURE (kpa) | 98.9 102,1 | DENSITY | 102,1 | |||||
TEMPERATURE (Deg c) | 19 | CALORIFIC VALUE | 42.5 MJ/kg | |||||
HUMIDITY (%) | 49 | LUB OIL SPEC | Multigrade | |||||
WIRING DIAGRAMS: | ||||||||
ENGINE | CONTROL PANEL(S) | |||||||
TESTED BY | lzawierowski | DATE | 22.04.2016 29.06.2011 |