Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E10425 CE:
RATED OUTPUT KVA RATING CLASSIFICATION PRP
KW
PHASE
VOLTS PERFORMANCE CLASS G1
AMPS (AS DEFINED BY ISO 8528-1)
HZ
RPM
GOVERNOR TYPE MECHANICAL COOLING METHOD
ENGINE MAKE PERKINS BUILD NUMBER DJ51434
ENGINE MODEL 1103A-33G SERIAL NUMBER U273863V
ALTERNATOR MAKE STAMFORD
ALTERNATOR MODEL PI144F SERIAL NUMBER 0269419/012
CONTROL PANEL(S) DSE7120 SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 50.4 400 32 22 - - 4.8
standby / prime+10% 110% 50.0 400 35 24 82 - 4.5
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 101.4 DENSITY 101.4
TEMPERATURE (Deg c) 17 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 72 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY hwalsh DATE 22.04.2016 05.04.2011