Generating Set Functional Test Report |
||||||||
In accordance with ISO 8528 - 6 2005 |
||||||||
PLANT NUMBER: | E10357 | CE: | ||||||
RATED OUTPUT | KVA | RATING CLASSIFICATION | PRP | |||||
KW | ||||||||
PHASE | ||||||||
VOLTS | PERFORMANCE CLASS | G1 | ||||||
AMPS | (AS DEFINED BY ISO 8528-1) | |||||||
HZ | ||||||||
RPM | ||||||||
GOVERNOR TYPE | MECHANICAL | COOLING METHOD | ||||||
ENGINE MAKE | PERKINS | BUILD NUMBER | DJ51434 | |||||
ENGINE MODEL | 1103A-33G | SERIAL NUMBER | U272852 | |||||
ALTERNATOR MAKE | NEWAGE | |||||||
ALTERNATOR MODEL | PI144H | SERIAL NUMBER | 0278122/002 | |||||
CONTROL PANEL(S) | DSE 7220 | SERIAL NUMBER(S) | ||||||
SWITCHGEAR | SERIAL NUMBER(S) | |||||||
LOAD TEST RESULTS (AT UNITY POWER FACTOR) | ||||||||
LOAD | HZ | VOLTS | AMPS | KW | ENGINE | OIL | OIL | |
type | % | TEMP | TEMP | PRESS | ||||
DEG C | DEG C | BAR | ||||||
load acceptance | % | 50,3 | 230 | 62,6 | 14,4 | 4,9 | ||
standby / prime+10% | 110% | 50.0 | 230 | 76,5 | 17,6 | 82 | 4,4 | |
GENERATING SET ENCLOSURE MECHANICAL PROTECTION AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M) (UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD IN ACCORDANCE WITH ISO8528-10) |
IP | |||||||
AMBIENT TEST CONDITIONS | FUEL/OIL USED | |||||||
ALTITUDE (M) | Sea Level | FUEL SPEC | BS2869A2 | |||||
BAROMETRIC PRESSURE (kpa) | 98.9 100,8 | DENSITY | 100,8 | |||||
TEMPERATURE (Deg c) | 13 | CALORIFIC VALUE | 42.5 MJ/kg | |||||
HUMIDITY (%) | 72 | LUB OIL SPEC | Multigrade | |||||
WIRING DIAGRAMS: | ||||||||
ENGINE | CONTROL PANEL(S) | |||||||
TESTED BY | lzawierowski | DATE | 22.04.2016 30.03.2011 |