Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E12230/D CE: NO
RATED OUTPUT KVA 30 RATING CLASSIFICATION PRP
KW 24
PHASE 3
VOLTS 400/230 PERFORMANCE CLASS G1
AMPS 43 (AS DEFINED BY ISO 8528-1)
HZ 50
RPM 1500
GOVERNOR TYPE MECHANICAL COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER DJ32038
ENGINE MODEL 1103A-33G SERIAL NUMBER U449592A
ALTERNATOR MAKE MECCALTE
ALTERNATOR MODEL ECP28-VL/4 SERIAL NUMBER 0001890537
CONTROL PANEL(S) 7110 MK2 SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 50 400/230 31 22 5.30
standby / prime+10% 110% 50 400/230 38 26 82 4.75
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
75
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 101.5 DENSITY 101.5
TEMPERATURE (Deg c) 8 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 93 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY kevin DATE 22.04.2016 14.12.2015