Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E13073 CE: NO
RATED OUTPUT KVA 30 RATING CLASSIFICATION PRP
KW 24
PHASE 3
VOLTS 415/240 PERFORMANCE CLASS G1
AMPS 42 (AS DEFINED BY ISO 8528-1)
HZ 50.0
RPM 1500
GOVERNOR TYPE MECHANICAL COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER DJ32003
ENGINE MODEL 1103A-33G SERIAL NUMBER U490370C
ALTERNATOR MAKE STAMFORD
ALTERNATOR MODEL PM144J SERIAL NUMBER G17B086072
CONTROL PANEL(S) 7120MKII SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 50.4 415 27 19 4.2
standby / prime+10% 110% 50.0 415 37 26 81 3.8
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
75
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 101.3 DENSITY 101.3
TEMPERATURE (Deg c) 7 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 87 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY ijohnson DATE 22.04.2016 28.01.2018