Generating Set Functional Test Report |
||||||||
In accordance with ISO 8528 - 6 2005 |
||||||||
PLANT NUMBER: | E12385/A | CE: | NO | |||||
RATED OUTPUT | KVA | 30 | RATING CLASSIFICATION | PRP | ||||
KW | 24 | |||||||
PHASE | 3 | |||||||
VOLTS | 400/230 | PERFORMANCE CLASS | G1 | |||||
AMPS | 43 | (AS DEFINED BY ISO 8528-1) | ||||||
HZ | 50.0 | |||||||
RPM | 1500 | |||||||
GOVERNOR TYPE | MECHANICAL | COOLING METHOD | LIQUID | |||||
ENGINE MAKE | PERKINS | BUILD NUMBER | DJ32003 | |||||
ENGINE MODEL | 1103A-33G | SERIAL NUMBER | U465226B | |||||
ALTERNATOR MAKE | STAMFORD | |||||||
ALTERNATOR MODEL | PI144G | SERIAL NUMBER | B15H339431 | |||||
CONTROL PANEL(S) | 7120 MKII | SERIAL NUMBER(S) | ||||||
SWITCHGEAR | SERIAL NUMBER(S) | |||||||
LOAD TEST RESULTS (AT UNITY POWER FACTOR) | ||||||||
LOAD | HZ | VOLTS | AMPS | KW | ENGINE | OIL | OIL | |
type | % | TEMP | TEMP | PRESS | ||||
DEG C | DEG C | BAR | ||||||
load acceptance | % | 50.7 | 400 | 28 | 19 | 4.4 | ||
standby / prime+10% | 110% | 50.0 | 400 | 38 | 26 | 78 | 4.1 | |
GENERATING SET ENCLOSURE MECHANICAL PROTECTION AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M) (UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD IN ACCORDANCE WITH ISO8528-10) |
IP | |||||||
AMBIENT TEST CONDITIONS | FUEL/OIL USED | |||||||
ALTITUDE (M) | Sea Level | FUEL SPEC | BS2869A2 | |||||
BAROMETRIC PRESSURE (kpa) | 98.9 100.2 | DENSITY | 100.2 | |||||
TEMPERATURE (Deg c) | 7 | CALORIFIC VALUE | 42.5 MJ/kg | |||||
HUMIDITY (%) | 71 | LUB OIL SPEC | Multigrade | |||||
WIRING DIAGRAMS: | ||||||||
ENGINE | CONTROL PANEL(S) | |||||||
TESTED BY | ijohnson | DATE | 22.04.2016 27.04.2016 |