Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E12832 CE: NO
RATED OUTPUT KVA 2000 RATING CLASSIFICATION PRP
KW 1600
PHASE 3
VOLTS 415/240 PERFORMANCE CLASS G1
AMPS 2782 (AS DEFINED BY ISO 8528-1)
HZ 50
RPM 1500
GOVERNOR TYPE ELECTRONIC COOLING METHOD R RAD
ENGINE MAKE PERKINS BUILD NUMBER DGWR8581
ENGINE MODEL 4016-61TRG2 SERIAL NUMBER U11380C
ALTERNATOR MAKE STAMFORD
ALTERNATOR MODEL PI734F SERIAL NUMBER A17A038759
CONTROL PANEL(S) DSE 7320 MKII SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 50.0 415 1113 800 9.1
standby / prime+10% 110% 50.0 415 2448 1760 82/83 4.7
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
85
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 101.6 DENSITY 101.6
TEMPERATURE (Deg c) 12 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 100 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY hwalsh DATE 22.04.2016 23.10.2017