Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E12363 CE: NO
RATED OUTPUT KVA 2000 RATING CLASSIFICATION PRP
KW 1600
PHASE 3
VOLTS 400/230 PERFORMANCE CLASS G1
AMPS 2890 (AS DEFINED BY ISO 8528-1)
HZ 50
RPM 1500
GOVERNOR TYPE ELECTRONIC COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER DGWR8581
ENGINE MODEL 4016-61 TRG2 SERIAL NUMBER U10110B
ALTERNATOR MAKE STAMFORD
ALTERNATOR MODEL PI734F SERIAL NUMBER A15H332642
CONTROL PANEL(S) DSE 7320 SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 50.0 400 1156 800 38/40 5.6
standby / prime+10% 110% 50.0 400 2543 1760 72/73 4.9
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 98.9 DENSITY 98.9
TEMPERATURE (Deg c) 10 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 86 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY hwalsh DATE 22.04.2016 22.04.2016