Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E12674 CE: NO
RATED OUTPUT KVA 1250 RATING CLASSIFICATION PRP
KW 1000
PHASE 3
VOLTS 415/240 PERFORMANCE CLASS G1
AMPS 1741 (AS DEFINED BY ISO 8528-1)
HZ 50
RPM 1500
GOVERNOR TYPE ELECTRONIC COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER DGKM6321
ENGINE MODEL 4012-46TWG2A SERIAL NUMBER U10490B
ALTERNATOR MAKE MECC-ALTE
ALTERNATOR MODEL ECO 43-2L4 SERIAL NUMBER 0001971720
CONTROL PANEL(S) DSE 7310 MKII SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 50.0 415 696 500 38/42 5.8
standby / prime+10% 110% 50.0 415 1532 1100 69/71 4.6
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 102.5 DENSITY 102.5
TEMPERATURE (Deg c) 2 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 98 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY hwalsh DATE 22.04.2016 27.01.2017