Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E12818 CE: NO
RATED OUTPUT KVA 800 RATING CLASSIFICATION PRP
KW 640
PHASE 3
VOLTS 400/230 PERFORMANCE CLASS G1
AMPS 1154 (AS DEFINED BY ISO 8528-1)
HZ 50
RPM 1500
GOVERNOR TYPE ELECTRONIC COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER DGDF6165
ENGINE MODEL 4006-23TAG3A SERIAL NUMBER U11067C
ALTERNATOR MAKE STAMFORD
ALTERNATOR MODEL HCI634G SERIAL NUMBER A17H326537
CONTROL PANEL(S) DSE 8620 SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 50.0 400 610 422 45 5.5
standby / prime+10% 110% 50.0 400 1016 704 82 4.4
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
85
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 101.5 DENSITY 101.5
TEMPERATURE (Deg c) 9 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 90 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY hwalsh DATE 22.04.2016 15.11.2017