Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E12322 CE: NO
RATED OUTPUT KVA 800 RATING CLASSIFICATION PRP
KW 640
PHASE 3
VOLTS 415/240 PERFORMANCE CLASS G1
AMPS 1114 (AS DEFINED BY ISO 8528-1)
HZ 50
RPM 1500
GOVERNOR TYPE ELECTRONIC COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER DGDF6165
ENGINE MODEL 4006-23TAG3A SERIAL NUMBER U10474B
ALTERNATOR MAKE MECC-ALTE
ALTERNATOR MODEL ECO 43-2S4 SERIAL NUMBER 0001902502
CONTROL PANEL(S) DSE 7310 SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 50.0 415 446 320 3 6.7
standby / prime+10% 110% 50.0 415 981 704 71 4.6
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 101.1 DENSITY 101.1
TEMPERATURE (Deg c) 10 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 87 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY hwalsh DATE 22.04.2016 06.04.2016