Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E10801 CE: NO
RATED OUTPUT KVA 900 RATING CLASSIFICATION ESP
KW 720
PHASE 3
VOLTS 400/230 PERFORMANCE CLASS G1
AMPS 1301 (AS DEFINED BY ISO 8528-1)
HZ 50
RPM 1500
GOVERNOR TYPE MECHANICAL COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER DGDF6116
ENGINE MODEL 4006C-23TAG3A SERIAL NUMBER U22518V
ALTERNATOR MAKE STAMFORD
ALTERNATOR MODEL HCI634H SERIAL NUMBER 0283181/028
CONTROL PANEL(S) DSE 7220 SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 50.0 400 676 468 - - 5.6
standby / prime+10% 100% 50.0 400 1040 720 71 - 4.7
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 100.4 DENSITY 100.4
TEMPERATURE (Deg c) 1 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 93 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY hwalsh DATE 22.04.2016 17.12.2011