Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E10395 CE:
RATED OUTPUT KVA 800 RATING CLASSIFICATION PRP
KW 640
PHASE 3
VOLTS 415/240 PERFORMANCE CLASS G1
AMPS 1113 (AS DEFINED BY ISO 8528-1)
HZ 50
RPM 1500
GOVERNOR TYPE ELECTRONIC COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER DGDF6002
ENGINE MODEL 400623TAG3A SERIAL NUMBER U11685V
ALTERNATOR MAKE MECCALTE
ALTERNATOR MODEL ECO432S SERIAL NUMBER 0001450956
CONTROL PANEL(S) 7110 SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 50.0 415 534 384 5.8
standby / prime+10% 110% 50.0 415 979 704 73 5.3
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 101.2 DENSITY 101.2
TEMPERATURE (Deg c) 12 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 54 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY ijohnson DATE 22.04.2016 20.05.2011