Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E12188/A CE: NO
RATED OUTPUT KVA 2000 RATING CLASSIFICATION PRP
KW 1600
PHASE 3
VOLTS 415/240 PERFORMANCE CLASS G1
AMPS 2783 (AS DEFINED BY ISO 8528-1)
HZ 50.0
RPM 1500
GOVERNOR TYPE ELECTRONIC COOLING METHOD HEAT EXCHANGER
ENGINE MAKE PERKINS BUILD NUMBER DGBR6258
ENGINE MODEL 4016-TAG2A SERIAL NUMBER U10827A
ALTERNATOR MAKE STAMFORD
ALTERNATOR MODEL PI734F SERIAL NUMBER A15I377154
CONTROL PANEL(S) 8610 SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance 57% 50.0 415 1269 912 6.1
standby / prime+10% 110% 50.0 415 2449 1760 78 4.4
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 100.2 DENSITY 100.2
TEMPERATURE (Deg c) 12 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 75 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY ijohnson DATE 22.04.2016 30.10.2015