Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E13235 CE: NO
RATED OUTPUT KVA 1650 RATING CLASSIFICATION STANDBY
KW 1320
PHASE 3
VOLTS 400/230 PERFORMANCE CLASS G1
AMPS 2382 (AS DEFINED BY ISO 8528-1)
HZ 50.0
RPM 1500
GOVERNOR TYPE ELECTRONIC COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER DGBM6311
ENGINE MODEL 4012-46TAG2A SERIAL NUMBER U12928C
ALTERNATOR MAKE STAMFORD
ALTERNATOR MODEL PI734D SERIAL NUMBER A16L506672
CONTROL PANEL(S) 7320MKII SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance 60% 50.0 400 1143 792 4.9
standby / prime+10% 110% 50.0 400 1906 1320 82 4.1
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 101.8 DENSITY 101.8
TEMPERATURE (Deg c) 16 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 84 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY ijohnson DATE 22.04.2016 03.09.2018