Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E11135/B CE: NO
RATED OUTPUT KVA 1505 RATING CLASSIFICATION PRP
KW 1204
PHASE 3
VOLTS 400/230 PERFORMANCE CLASS G1
AMPS 2172 (AS DEFINED BY ISO 8528-1)
HZ 50
RPM 1500
GOVERNOR TYPE ELECTRONIC COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER DGBM6137
ENGINE MODEL 4012-46TAG2A SERIAL NUMBER U11888W
ALTERNATOR MAKE STAMFORD
ALTERNATOR MODEL PI734C SERIAL NUMBER 0276638/004
CONTROL PANEL(S) NONE SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 50.0 400 1234 855 5.4
standby / prime+10% 110% 50.0 400 1911 1324 74 4.3
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 101.5 DENSITY 101.5
TEMPERATURE (Deg c) 9 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 93 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY ijohnson DATE 22.04.2016 13.11.2012