Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E13088/F CE: NO
RATED OUTPUT KVA 1000 RATING CLASSIFICATION PRP
KW 800
PHASE 3
VOLTS 400/230 PERFORMANCE CLASS G1
AMPS 1445 (AS DEFINED BY ISO 8528-1)
HZ 50
RPM 1500
GOVERNOR TYPE ELECTRONIC COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER DGBH6249
ENGINE MODEL 4008TAG2A SERIAL NUMBER U13000C
ALTERNATOR MAKE STAMFORD
ALTERNATOR MODEL HCI634J SERIAL NUMBER A17H337005
CONTROL PANEL(S) DSE 8610 SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 50.0 400 578 400 36 5.8
standby / prime+10% 110% 50.0 400 1272 880 83 4.4
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 100.6 DENSITY 100.6
TEMPERATURE (Deg c) 6 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 98 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY hwalsh DATE 22.04.2016 27.01.2018