Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E11441/C CE: NO
RATED OUTPUT KVA 995 RATING CLASSIFICATION PRP
KW 796
PHASE 3
VOLTS 220/127 PERFORMANCE CLASS G1
AMPS 2611 (AS DEFINED BY ISO 8528-1)
HZ 60.0
RPM 1800
GOVERNOR TYPE ELECTRONIC COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER DGBH6161
ENGINE MODEL 4008TAG2A SERIAL NUMBER U17061X
ALTERNATOR MAKE STAMFORD
ALTERNATOR MODEL HCI634H SERIAL NUMBER A13J405279
CONTROL PANEL(S) 7220 SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance 55% 60.0 220 1149 438 5.8
standby / prime+10% 110% 60.0 220 2298 876 74 5.2
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 101.7 DENSITY 101.7
TEMPERATURE (Deg c) 12 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 83 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY ijohnson DATE 22.04.2016 09.10.2013