Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E10210 CE:
RATED OUTPUT KVA RATING CLASSIFICATION PRP
KW
PHASE
VOLTS PERFORMANCE CLASS G1
AMPS (AS DEFINED BY ISO 8528-1)
HZ
RPM
GOVERNOR TYPE ELECTRONIC COOLING METHOD
ENGINE MAKE PERKINS BUILD NUMBER DGBH6127
ENGINE MODEL 4008TAG2A SERIAL NUMBER U10245V
ALTERNATOR MAKE STAMFORD
ALTERNATOR MODEL HCI634J SERIAL NUMBER 0260177/020
CONTROL PANEL(S) 7210 SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 50 415 634 456 5.4
standby / prime+10% 110% 50 415 1224 880 72 4.8
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
103
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 101.9 DENSITY 101.9
TEMPERATURE (Deg c) 2 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 100 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY ijohnson DATE 22.04.2016 01.02.2011