Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E10565 CE: NO
RATED OUTPUT KVA 745 RATING CLASSIFICATION PRP
KW 596
PHASE 3
VOLTS 380/220 PERFORMANCE CLASS G1
AMPS 1132 (AS DEFINED BY ISO 8528-1)
HZ 50
RPM 1500
GOVERNOR TYPE ELECTRONIC COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER DGBF6118
ENGINE MODEL 4006-23TAG2A SERIAL NUMBER U17731V
ALTERNATOR MAKE STAMFORD
ALTERNATOR MODEL HCI634G SERIAL NUMBER 0278843/001
CONTROL PANEL(S) DSE 7220 SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance 69%% 50.0 380 625 411 - - 5.4
standby / prime+10% 110% 50.0 380 996 656 70 - 4.8
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 102.5 DENSITY 102.5
TEMPERATURE (Deg c) 17 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 55 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY hwalsh DATE 22.04.2016 29.07.2011