Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E10421 CE:
RATED OUTPUT KVA 745 RATING CLASSIFICATION PRP
KW 596
PHASE 3
VOLTS 400/230 PERFORMANCE CLASS G1
AMPS 1075 (AS DEFINED BY ISO 8528-1)
HZ 50
RPM 1500
GOVERNOR TYPE ELECTRONIC COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER DGBF6118
ENGINE MODEL 4006C23TAG2A SERIAL NUMBER U14417V
ALTERNATOR MAKE STAMFORD
ALTERNATOR MODEL HCI634G SERIAL NUMBER 0278912/005
CONTROL PANEL(S) 7220 SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 50.0 400 594 411 5.4
standby / prime+10% 110% 50.0 400 946 657 73 5.1
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 102.0 DENSITY 102.0
TEMPERATURE (Deg c) 15 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 45 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY ijohnson DATE 22.04.2016 24.05.2011