Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E10484 CE: NO
RATED OUTPUT KVA 910 RATING CLASSIFICATION PRP
KW 728
PHASE 3
VOLTS 380/220 PERFORMANCE CLASS G1
AMPS 1383 (AS DEFINED BY ISO 8528-1)
HZ 50
RPM 1500
GOVERNOR TYPE ELECTRONIC COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER DGAH6019
ENGINE MODEL 4008TG1A SERIAL NUMBER U15041V
ALTERNATOR MAKE STAMFORD
ALTERNATOR MODEL HCI 634J SERIAL NUMBER 0276616/010
CONTROL PANEL(S) COMAP IC-NT INTELLI SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance 64%% 50.0 380 466 708 - - 4.8
standby / prime+10% 110% 50.0 380 801 1217 79 - 4.3
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 100.9 DENSITY 100.9
TEMPERATURE (Deg c) 14 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 82 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY hwalsh DATE 22.04.2016 25.07.2011