Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E10482 CE:
RATED OUTPUT KVA 910 RATING CLASSIFICATION PRP
KW 728
PHASE 3
VOLTS 380/220 PERFORMANCE CLASS G1
AMPS 1383 (AS DEFINED BY ISO 8528-1)
HZ 50
RPM 1500
GOVERNOR TYPE ELECTRONIC COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER DGAH6019
ENGINE MODEL 4008TAG1A SERIAL NUMBER U16405V
ALTERNATOR MAKE STAMFORD
ALTERNATOR MODEL HCI634H SERIAL NUMBER 0269628/004
CONTROL PANEL(S) COMAP AMF25 SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 50.0 380 664 437 5.2
standby / prime+10% 110% 50.0 380 1217 801 70 4.4
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 100.6 DENSITY 100.6
TEMPERATURE (Deg c) 17 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 77 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY ijohnson DATE 22.04.2016 09.07.2011