Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E11509 CE: NO
RATED OUTPUT KVA 5 RATING CLASSIFICATION PRP
KW 4
PHASE 1
VOLTS 230 PERFORMANCE CLASS G1
AMPS 22 (AS DEFINED BY ISO 8528-1)
HZ 50.0
RPM 1500
GOVERNOR TYPE MECHANICAL COOLING METHOD AIR
ENGINE MAKE LISTER BUILD NUMBER A08
ENGINE MODEL TR1 SERIAL NUMBER 1400577
ALTERNATOR MAKE MECC-ALTE
ALTERNATOR MODEL ECP28-S4 SERIAL NUMBER 1709234
CONTROL PANEL(S) DSE 7110 SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 50.0 230 9 2 2.1
standby / prime+10% 110% 50.0 230 19 4.4 1.4
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 100.1 DENSITY 100.1
TEMPERATURE (Deg c) 11 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 60 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY grustill DATE 22.04.2016 27.03.2014