Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E13069 CE: NO
RATED OUTPUT KVA 500 RATING CLASSIFICATION PRP
KW 400
PHASE 3
VOLTS 400/230 PERFORMANCE CLASS G1
AMPS 723 (AS DEFINED BY ISO 8528-1)
HZ 50
RPM 1500
GOVERNOR TYPE ECU COOLING METHOD LIQUID
ENGINE MAKE CUMMINS BUILD NUMBER 8588
ENGINE MODEL QSX15G8 SERIAL NUMBER 80029924
ALTERNATOR MAKE STAMFORD
ALTERNATOR MODEL HCI544C SERIAL NUMBER A17L497877
CONTROL PANEL(S) DSE 7120MKII SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 50.0 400 289 200 6 3.4
standby / prime+10% 110% 50.0 400 696 440 82 2.7
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 102.3 DENSITY 102.3
TEMPERATURE (Deg c) 0 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 89 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY hwalsh DATE 22.04.2016 28.02.2018