Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E10994 CE: N0
RATED OUTPUT KVA 1000 RATING CLASSIFICATION PRP
KW 800
PHASE 3
VOLTS 415/240 PERFORMANCE CLASS G1
AMPS 1391 (AS DEFINED BY ISO 8528-1)
HZ 50
RPM 1500
GOVERNOR TYPE E.C.M. COOLING METHOD LIQUID
ENGINE MAKE CUMMINS BUILD NUMBER 3638242
ENGINE MODEL QST30G4 SERIAL NUMBER 37254120
ALTERNATOR MAKE MECC-ALTE
ALTERNATOR MODEL ECO43-1L/4 SERIAL NUMBER 1621342
CONTROL PANEL(S) 7110 SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance 60% 50.0 415 668 480 5.9
standby / prime+10% 110% 50.0 415 1224 880 79 86 4.0
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 101.8 DENSITY 101.8
TEMPERATURE (Deg c) 19 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 82 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY ijohnson DATE 22.04.2016 22.08.2012