Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E13120/B CE: NO
RATED OUTPUT KVA 1600 RATING CLASSIFICATION PRP
KW 1280
PHASE 3
VOLTS 415/240 PERFORMANCE CLASS G1
AMPS 2228 (AS DEFINED BY ISO 8528-1)
HZ 50
RPM 1500
GOVERNOR TYPE ECU COOLING METHOD LIQUID
ENGINE MAKE CUMMINS BUILD NUMBER
ENGINE MODEL QSK50G7 SERIAL NUMBER 33213984
ALTERNATOR MAKE STAMFORD
ALTERNATOR MODEL PI734D SERIAL NUMBER A18C123555
CONTROL PANEL(S) DSE 7320 MKII SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance 50% 50 415 891 640 62 5.8
standby / prime+10% 110% 50 415 1961 1408 81 4.5
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 101.2 DENSITY 101.2
TEMPERATURE (Deg c) 22 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 58 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY hwalsh DATE 22.04.2016 02.07.2018