Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E13119 CE: YES
RATED OUTPUT KVA 1000 RATING CLASSIFICATION PRP
KW 800
PHASE 3
VOLTS 400/230 PERFORMANCE CLASS G1
AMPS 1445 (AS DEFINED BY ISO 8528-1)
HZ 50
RPM 1500
GOVERNOR TYPE ELECTRONIC COOLING METHOD LIQUID
ENGINE MAKE CUMMINS BUILD NUMBER
ENGINE MODEL KTA38G5 SERIAL NUMBER 25436350
ALTERNATOR MAKE STAMFORD
ALTERNATOR MODEL HCI634J SERIAL NUMBER A17H337155
CONTROL PANEL(S) TBOX SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance 50% 50.0 400 578 400 45 7.6
standby / prime+10% 110% 50.0 400 1272 880 80 4.9
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 101.8 DENSITY 101.8
TEMPERATURE (Deg c) 22 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 46 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY hwalsh DATE 22.04.2016 19.07.2018