Generating Set Functional Test Report |
||||||||
In accordance with ISO 8528 - 6 2005 |
||||||||
| PLANT NUMBER: | E13096/A | CE: | NO | |||||
| RATED OUTPUT | KVA | 1615 | RATING CLASSIFICATION | ESP | ||||
| KW | 1292 | |||||||
| PHASE | 3 | |||||||
| VOLTS | 400/230 | PERFORMANCE CLASS | G1 | |||||
| AMPS | 2334 | (AS DEFINED BY ISO 8528-1) | ||||||
| HZ | 50 | |||||||
| RPM | 1500 | |||||||
| GOVERNOR TYPE | ECU | COOLING METHOD | LIQUID | |||||
| ENGINE MAKE | CUMMINS | BUILD NUMBER | ||||||
| ENGINE MODEL | QSK50G4 | SERIAL NUMBER | 33213049 | |||||
| ALTERNATOR MAKE | STAMFORD | |||||||
| ALTERNATOR MODEL | PI734C | SERIAL NUMBER | A14H342526 | |||||
| CONTROL PANEL(S) | DSE 8610 MKII | SERIAL NUMBER(S) | ||||||
| SWITCHGEAR | SERIAL NUMBER(S) | |||||||
| LOAD TEST RESULTS (AT UNITY POWER FACTOR) | ||||||||
| LOAD | HZ | VOLTS | AMPS | KW | ENGINE | OIL | OIL | |
| type | % | TEMP | TEMP | PRESS | ||||
| DEG C | DEG C | BAR | ||||||
| load acceptance | % | 50 | 400 | 934 | 646 | 28 | 29 | 6.0 |
| standby / prime+10% | 100% | 50 | 400 | 1867 | 1292 | 82 | 99 | 4.5 |
|
GENERATING SET ENCLOSURE MECHANICAL PROTECTION AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M) (UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD IN ACCORDANCE WITH ISO8528-10) |
IP | |||||||
| AMBIENT TEST CONDITIONS | FUEL/OIL USED | |||||||
| ALTITUDE (M) | Sea Level | FUEL SPEC | BS2869A2 | |||||
| BAROMETRIC PRESSURE (kpa) | 98.9 101.2 | DENSITY | 101.2 | |||||
| TEMPERATURE (Deg c) | 16 | CALORIFIC VALUE | 42.5 MJ/kg | |||||
| HUMIDITY (%) | 98 | LUB OIL SPEC | Multigrade | |||||
| WIRING DIAGRAMS: | ||||||||
| ENGINE | CONTROL PANEL(S) | |||||||
| TESTED BY | hwalsh | DATE | 22.04.2016 25.05.2018 | |||||