Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E11123/C CE: NO
RATED OUTPUT KVA 150 RATING CLASSIFICATION PRP
KW 120
PHASE 3
VOLTS 415/240 PERFORMANCE CLASS G1
AMPS 208 (AS DEFINED BY ISO 8528-1)
HZ 50
RPM 1500
GOVERNOR TYPE ELECTRONIC COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER
ENGINE MODEL 1006 TAG2 SERIAL NUMBER
ALTERNATOR MAKE MECC-ALTE
ALTERNATOR MODEL ECP342S4 SERIAL NUMBER
CONTROL PANEL(S) DSE 7120 SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance 60% 50 415 83 60
standby / prime+10% 110% 50 415 182 132
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
85
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 DENSITY
TEMPERATURE (Deg c) CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY michael DATE 22.04.2016 26.10.2012