Generating Set Functional Test Report |
||||||||
In accordance with ISO 8528 - 6 2005 |
||||||||
PLANT NUMBER: | E10396 | CE: | ||||||
RATED OUTPUT | KVA | 1000 | RATING CLASSIFICATION | PRP | ||||
KW | 800 | |||||||
PHASE | 3 | |||||||
VOLTS | 400/230 | PERFORMANCE CLASS | G1 | |||||
AMPS | 1443 | (AS DEFINED BY ISO 8528-1) | ||||||
HZ | 50 | |||||||
RPM | 1500 | |||||||
GOVERNOR TYPE | ECM | COOLING METHOD | LIQUID | |||||
ENGINE MAKE | CUMMINS | BUILD NUMBER | ||||||
ENGINE MODEL | QST30G4 | SERIAL NUMBER | 37246766 | |||||
ALTERNATOR MAKE | MECCALTE | |||||||
ALTERNATOR MODEL | ECO431LN4 | SERIAL NUMBER | 0001472122 | |||||
CONTROL PANEL(S) | 7110 | SERIAL NUMBER(S) | ||||||
SWITCHGEAR | SERIAL NUMBER(S) | |||||||
LOAD TEST RESULTS (AT UNITY POWER FACTOR) | ||||||||
LOAD | HZ | VOLTS | AMPS | KW | ENGINE | OIL | OIL | |
type | % | TEMP | TEMP | PRESS | ||||
DEG C | DEG C | BAR | ||||||
load acceptance | % | 50.0 | 400 | 577 | 400 | 5.6 | ||
standby / prime+10% | 110% | 50.0 | 400 | 1270 | 880 | 77 | 86 | 4.5 |
GENERATING SET ENCLOSURE MECHANICAL PROTECTION AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M) (UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD IN ACCORDANCE WITH ISO8528-10) |
IP | |||||||
AMBIENT TEST CONDITIONS | FUEL/OIL USED | |||||||
ALTITUDE (M) | Sea Level | FUEL SPEC | BS2869A2 | |||||
BAROMETRIC PRESSURE (kpa) | 98.9 100.6 | DENSITY | 100.6 | |||||
TEMPERATURE (Deg c) | 17 | CALORIFIC VALUE | 42.5 MJ/kg | |||||
HUMIDITY (%) | 59 | LUB OIL SPEC | Multigrade | |||||
WIRING DIAGRAMS: | ||||||||
ENGINE | CONTROL PANEL(S) | |||||||
TESTED BY | ijohnson | DATE | 22.04.2016 17.06.2011 |