Generating Set Functional Test Report |
||||||||
In accordance with ISO 8528 - 6 2005 |
||||||||
PLANT NUMBER: | E111/A | CE: | NO | |||||
RATED OUTPUT | KVA | 100 | RATING CLASSIFICATION | ESP | ||||
KW | 10.4 | |||||||
PHASE | 1 | |||||||
VOLTS | 208/120 | PERFORMANCE CLASS | G1 | |||||
AMPS | 10.8 | (AS DEFINED BY ISO 8528-1) | ||||||
HZ | 50 | |||||||
RPM | 1500 | |||||||
GOVERNOR TYPE | ECU | COOLING METHOD | H EX | |||||
ENGINE MAKE | CUMMINS | BUILD NUMBER | 10282-5 | |||||
ENGINE MODEL | 1103A-33G | SERIAL NUMBER | 16701003220 | |||||
ALTERNATOR MAKE | MECC-ALTE | |||||||
ALTERNATOR MODEL | ECO 32-2M4 | SERIAL NUMBER | A16C120132 | |||||
CONTROL PANEL(S) | COMAP AMF25 | SERIAL NUMBER(S) | ||||||
SWITCHGEAR | SERIAL NUMBER(S) | |||||||
LOAD TEST RESULTS (AT UNITY POWER FACTOR) | ||||||||
LOAD | HZ | VOLTS | AMPS | KW | ENGINE | OIL | OIL | |
type | % | TEMP | TEMP | PRESS | ||||
DEG C | DEG C | BAR | ||||||
load acceptance | 100% | 50 | 208 | 104 | 10 | 0 | 10 | 3.3 |
standby / prime+10% | 110% | 50 | 208 | 100 | 10 | 3.5 | 100 | 2.5 |
GENERATING SET ENCLOSURE MECHANICAL PROTECTION AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M) (UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD IN ACCORDANCE WITH ISO8528-10) |
IP | |||||||
100.1 | ||||||||
AMBIENT TEST CONDITIONS | FUEL/OIL USED | |||||||
ALTITUDE (M) | Sea Level | FUEL SPEC | BS2869A2 | |||||
BAROMETRIC PRESSURE (kpa) | 98.9 100. | DENSITY | 100. | |||||
TEMPERATURE (Deg c) | 10 | CALORIFIC VALUE | 42.5 MJ/kg | |||||
HUMIDITY (%) | 44 | LUB OIL SPEC | Multigrade | |||||
WIRING DIAGRAMS: | ||||||||
ENGINE | CONTROL PANEL(S) | |||||||
TESTED BY | hwalsh | DATE | 22.04.2016 02.11.2018 |