Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E10158 CE:
RATED OUTPUT KVA RATING CLASSIFICATION G1
KW
PHASE
VOLTS PERFORMANCE CLASS PRP
AMPS (AS DEFINED BY ISO 8528-1)
HZ
RPM
GOVERNOR TYPE MECHANICAL COOLING METHOD
ENGINE MAKE PERKINS BUILD NUMBER
ENGINE MODEL 1006TG1A SERIAL NUMBER
ALTERNATOR MAKE MECC-ALTE
ALTERNATOR MODEL ECP34-2S SERIAL NUMBER
CONTROL PANEL(S) SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 50.6 380 95 63 5.3
standby / prime+10% 110% 50 380 139 92 82 4.7
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 100.4 DENSITY 100.4
TEMPERATURE (Deg c) 12 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 82 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY grustill DATE 22.04.2016 07.02.2011